Technical Specifications
|
|
Efficiency
|
|
Max. Efficiency
|
98.7%
|
European Efficiency
|
98.5%
|
Input
|
|
Max. Input Voltage
|
1,100 V
|
Max. Current per MPPT
|
22 A
|
Max. Short Circuit Current per MPPT
|
30A
|
Start Voltage
|
200 V
|
MPPT Operating Voltage Range
|
200 V ~ 1,000 V
|
Rated Input Voltage
|
600 V
|
Number of Inputs
|
12
|
Number of MPP Trackers
|
6
|
Output
|
|
Rated AC Active Power
|
50,000 W
|
Max. AC Apparent Power
|
50,000 VA
|
Max. AC Apparent Power
|
55,000 VA
|
Max. AC Active Power (cosφ=1)
|
55,000 W
|
Rated Output Voltage
|
220 V / 230 V, default 3W + N + PE; 380 V / 400 V, 3W + PE
|
Rated AC Grid Frequency
|
50 Hz / 60 Hz
|
Rated Output Current
|
76 A @380 V / 72.2 A @400 V
|
Max. Output Current
|
83.6 A @380 V / 79.4 A @400 V
|
Adjustable Power Factor Range
|
0.8 LG … 0.8 LD
|
Max. Total Harmonic Distortion
|
<3%
|
Protection
|
|
Input-side Disconnection Device
|
Yes
|
Anti-islanding Protection
|
Yes
|
AC Overcurrent Protection
|
Yes
|
DC Reverse-polarity Protection
|
Yes
|
PV-array String Fault Monitoring
|
Yes
|
DC Surge Arrester
|
Type II
|
AC Surge Arrester
|
Type II
|
DC Insulation Resistance Detection
|
Yes
|
Residual Current Monitoring Unit
|
Yes
|
Communication
|
|
Display
|
LED Indicators, Bluetooth + APP
|
USB
|
Yes
|
RS485
|
Yes
|
Monitoring BUS (MBUS)
|
Yes (isolation transformer required)
|
General Data
|
|
Dimensions (W x H x D)
|
1,075 x 555 x 300 mm (42.3 x 21.9 x 11.8 inch)
|
Weight (with mounting plate)
|
74 kg (163.1 lb.)
|
Operating Temperature Range
|
-25°C ~ 60°C (-13°F ~ 140°F)
|
Cooling Method
|
Natural Convection
|
Max. Operating Altitude
|
4,000 m (13,123 ft.)
|
Relative Humidity
|
0 ~ 100%
|
DC Connector
|
Amphenol Helios H4
|
AC Connector
|
Cable Gland + OT Terminal
|
Protection Degree
|
IP65
|
Topology
|
Transformerless
|
Nighttime Power Consumption
|
< 2 W
|
Country of Manufacture
|
China
|
Standard Compliance (more available uponrequest)
|
|
Certificate
|
N/IEC 62109-1, EN/IEC 62109-2, IEC 62116
|
Grid Code
|
AS/NZS 4777.2 2020
|
In medium-voltage grid-connected scenarios or non-low-voltage public grid-connected scenarios (industrial environment), the inverter is powered through a dedicated transformer and is not allowed to be connected to the low-voltage overhead grid.